IEA DHC AIIEA DHC AI

Absorption Refrigeration with Thermal Storage 1

PDF · 4 Dec 2025

Laboratory-scale experimental study (May 2002) of a novel absorption refrigeration system combined with a thermal (ice) storage (TIS) using vacuum freezing and a steam jet-pump. The report (authors Ian W. Eames and Jorge Caeiro) describes rig design, component specifications, TIS element construction (polymer-gel filled perforated baskets), and experimental campaigns measuring gel concentration, element layout, jet-pump entrainment and nozzle position, critical back-pressure, freezing performance and full-cycle operation. Key measured outcomes: optimum gel water content ≈98% w/w, jet-pump critical back-pressure ≈1.4 kPa, measured entrainment ratio ≈0.443, measured jet‑pump-only COP ≈0.469 and estimated design charging COP ≈0.38. The study concludes technical feasibility but recommends further instrumentation improvements and cost/lifecycle analysis and industry partnership for scale-up.

Questions this document answers

May 2002 (Date: 2002-05-1)

Ian W. Eames; Jorge Caeiro

90 5748 028 X

5 kW

Approximately 98.27% w/w water (reported ≈98%)

Related profiles

More from IEA

© 2026 Delphi · Terms · Privacy · Published by IEA DHC AI